A shear bolt lug for MV cable must fit more than the conductor cross-section. It also sits inside a termination system, connects to a defined equipment stud or pad, and occupies limited space in a switchgear or transformer box. A lug that accepts the cable may still be unusable if its body is too large for the insulating component, its palm hole does not match the stud, or the installed cable cannot maintain the required routing and clearances.
The safest purchasing method is to treat the cable, lug, termination kit, and equipment interface as one assembly. The termination kit manufacturer’s current installation instructions and written compatibility approval should take priority over a general lug catalogue.
| Selection gate | Data to provide | Evidence to obtain |
|---|---|---|
| Cable conductor | Copper or aluminium; cross-section; round or sector; solid, stranded, compacted, or flexible construction; actual conductor diameter | Model-specific conductor table and any insert requirement |
| Termination accessory | Brand, kit reference, voltage class, and heat-shrink, cold-shrink, slip-on, or separable design | Written compatibility confirmation or an approved component list |
| Equipment connection | Stud diameter, pad pattern, washer, bolt length, and terminal-pad material | Palm-hole and palm-dimension drawing |
| Installation envelope | Cable entry, bend direction, phase spacing, barriers, covers, and tool access | Installed envelope drawing or sample-fit approval |
| Project acceptance | Applicable project standard and required electrical, mechanical, and material records | Reports covering the exact offered model and declared conductor application |
Begin with the cable manufacturer’s data sheet, then compare suitable designs in the mechanical lugs and connectors range. Record conductor material, nominal cross-section, construction, shape, and measured diameter after insulation removal. Two cables with the same square-millimetre rating can have different diameters and strand behavior. Do not assume that a lug listed for 95 mm² accepts every solid, stranded, compacted, or flexible 95 mm² conductor.
CONWELL lists its BLMT shear-bolt mechanical lug family for low- and medium-voltage terminations up to 35 kV, with a combined family range of 25–630 mm². This is not one universal lug. The published model bands are BLMT-25/95-13 for 25–95 mm², BLMT-35/150-13 for 35–150 mm², BLMT-95/240-13 for 95–240 mm², BLMT-120/300-17 for 120–300 mm², BLMT-185/400-17 for 185–400 mm², and BLMT-500/630-17 for 500–630 mm². Select from the exact row, then ask the supplier to confirm the offered model against the named cable.

CONWELL BLMT shear bolt lug. Model approval should use the exact conductor band, not the 25–630 mm² family headline.
If an insert, centering sleeve, or conductor preparation method is required, include its part number and installation instruction in the quotation. Never remove strands or substitute an unapproved insert simply to make a cable fit.
The lug palm must match the actual equipment interface. State the stud nominal diameter and confirm the required clearance-hole diameter from the equipment drawing. Also record whether the pad uses one or two holes, the hole pitch, palm width and thickness, available edge distance, washer bearing area, tightening requirement, and terminal-pad material.
The CONWELL page publishes model suffixes ending in “13” or “17”, but an RFQ should not interpret a suffix as a guaranteed stud or hole size without a controlled dimensional drawing. Ask the supplier to state the finished palm-hole diameter for the exact offered reference. Field drilling, slotting, or enlarging can damage plating, reduce the bearing area, and invalidate the approved connection design.

The visible model marking and single-hole palm help receiving inspection, but the approved drawing must define the hole and palm dimensions.
For MV work, a shear bolt lug for MV cable operates inside an electrical insulation and stress-control system. The mechanical cable lug application overview can support initial product screening, but the termination manufacturer must confirm the lug reference, cable reference, and kit reference as a compatible combination. A statement such as “suitable for MV” is not enough.
The compatibility check should cover lug body outside diameter, barrel length, overall installed length, palm offset, surface finish, bolt-head projection after shear, sealing cap or filler arrangement, and the internal bore of the insulating component. These details affect whether cold-shrink, heat-shrink, slip-on, or molded parts seat as designed and whether air pockets or sharp transitions are avoided.
Separable connectors may require a special threaded, spade, or solid-pin interface rather than a conventional flat palm. State the accessory type first and do not substitute between interface families based only on the conductor range.

The barrel diameter, bolt position, and installed bolt remnant form part of the accessory envelope; obtain the exact dimensional drawing before approval.
Check the complete installed assembly, not the loose lug. The termination kit must have enough axial space to cover the prepared cable and connector as instructed. The equipment box must accommodate the lug palm, stud hardware, phase barriers, insulation cover, and cable bend without forcing the termination sideways.
Ask for a drawing that shows cable entry, termination length, lug orientation, palm-to-stud position, closest grounded metal, phase-to-phase spacing, and access for the approved installation tool. For compact switchgear, transformers, or multiple cables per phase, a sample assembly or first-article fit check can resolve conflicts before shipment.
| RFQ field | Required entry |
|---|---|
| Cable | Manufacturer, reference, voltage class, Cu/Al, mm², construction, shape, and conductor diameter |
| Termination | Manufacturer, kit reference, technology, and written lug compatibility requirement |
| Equipment | Stud/pad drawing, hole size, hardware, terminal material, and available space |
| Lug offer | Exact model, conductor range and constructions, inserts, palm dimensions, body dimensions, material, plating, and quantity |
| Installation | Cable preparation, bolt sequence, approved tools, shear-head acceptance, and training needs |
| Documents | Controlled drawing, data sheet, instructions, compatibility statement, traceability, and applicable test reports |
Do not use the shear-head break as evidence of equipment-stud torque. The shear bolt secures the conductor inside the barrel; the palm-to-equipment fastener is a separate joint governed by the equipment instructions.
Does a published conductor range cover every cable construction within those sizes?
No. A cross-section range does not automatically confirm solid, stranded, compacted, sector-shaped, or flexible conductors. Submit the cable data sheet and actual conductor diameter, then obtain model-specific confirmation of the supported construction and any required insert.
Do the “13” and “17” suffixes confirm the finished palm-hole diameter?
Do not approve the hole from the suffix alone. Request a controlled drawing that states the finished hole diameter, palm width, thickness, length, and offset for the exact offered reference, then compare it with the equipment stud and terminal-pad drawing.
Can any shear bolt lug for MV cable be used with any termination kit?
No. The termination manufacturer must confirm the cable, lug, and kit as a compatible combination. Body diameter, overall length, bolt remnant, surface condition, palm position, insulating-component bore, and stress-control geometry can prevent an otherwise suitable conductor connection from fitting the accessory.
Is a completed shear-head break enough to accept the installation?
No. It indicates completion of a designed bolt action only when the correct model, cable preparation, insert, bolt sequence, and tool conditions were used. Acceptance should also cover conductor condition, bolt remnants, accessory position, sealing, clearances, cable support, traceability, and the separately tightened equipment fastener.
The published BLMT page identifies a high-strength aluminium-alloy body, aluminium-alloy bolts, and a tin-plated surface. Project approval still requires model-specific drawings and confirmation of conductor construction, accessory fit, and equipment interface.
For a model and compatibility check, send CONWELL an MV lug enquiry with the cable data sheet, termination-kit reference, equipment drawing, quantity, and required approval documents. This gives engineering and procurement one traceable basis for selection and quotation.
Written by the CONWELL international trade team, led by Matt, General Manager, who brings more than 20 years of international trade experience and deep expertise in the power fittings industry. He also leads CONWELL's CNAS laboratory, overseeing product testing, quality control, and technical compliance.
TEL: +86-158-5877-7327
No. 16, Waixi Road, Lingang Economic Development Zone, Yueqing Bay Port Area, Yueqing City, Wenzhou City, Zhejiang Province, China
COPYRIGHT © 2025 ZHEJIANG KEYI ELECTRIC GROUP CO., LTD. ALL RIGHTS RESERVED.
We value your privacy
We use cookies to enhance your browsing experience, serve personalised ads or content, and analyse our traffic. By clicking "Accept All", you consent to our use of cookies.
Customise Consent Preferences
We use cookies to help you navigate efficiently and perform certain functions. You will find detailed information about all cookies under each consent category below.
The cookies that are categorised as "Necessary" are stored on your browser as they are essential for enabling the basic functionalities of the site. Show more
Necessary cookies are required to enable the basic features of this site, such as providing secure log-in or adjusting your consent preferences. These cookies do not store any personally identifiable data.
Functional cookies help perform certain functionalities like sharing the content of the website on social media platforms, collecting feedback, and other third-party features.
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics such as the number of visitors, bounce rate, traffic source, etc.
Performance cookies are used to understand and analyse the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Advertisement cookies are used to provide visitors with customised advertisements based on the pages you visited previously and to analyse the effectiveness of the ad campaigns.