A mechanical lug can match the cable cross-section and still be unusable at the equipment. The usual causes are an unsupported conductor construction, a palm hole that does not fit the stud, a palm that is too wide for the terminal pad, or a barrel that interferes with phase barriers and cable bending space. This mechanical cable lug selection guide turns those interfaces into purchasing fields for switchgear, transformer, motor, and busbar terminations.
Start with the cable data sheet and the equipment terminal drawing. Then select from a verified mechanical cable lug range. Do not approve a lug from its headline cross-sectional range alone.
| Selection check | Information required | Risk if omitted |
|---|---|---|
| Conductor material | Copper or aluminum; bare or plated; equipment terminal material | Unsupported metal interface, oxidation, or unstable contact |
| Conductor construction | Round or sector; solid, stranded, compacted, or flexible class | Incorrect barrel fill or bolt contact |
| Approved range | Exact model range for that material and construction | A nominally correct mm² size may sit outside the tested combination |
| Palm interface | Stud diameter, hole count, hole diameter, pitch, palm width and thickness | The lug cannot seat flat or cannot be bolted to the equipment |
| Installation envelope | Overall length, barrel diameter, offset, phase clearance and cable bend radius | Interference with barriers, covers, adjacent phases, or the cable route |
The first interface is conductor-to-barrel. The second is palm-to-equipment pad. Record the cable conductor material and the terminal pad or busbar material separately.

A bimetal lug illustrates why the conductor-side and equipment-side materials must be specified separately.
“240 mm² aluminum cable” is not a complete selection description. A 240 mm² round stranded conductor, compacted conductor, and sector conductor do not necessarily present the same geometry inside a lug. Solid and flexible conductors create additional differences in contact behavior.
Use the cable manufacturer’s designation and drawing to state:
Do not assume a sector conductor may be rounded before insertion. Pre-rounding, inserts, centering rings, or other preparation must follow the selected lug’s instructions. Fine-stranded conductors also require explicit approval; a range tested for conventional power-cable conductors should not be extended to flexible cable by inference.
A broad family range describes the catalogue, not one universal lug. CONWELL’s BLMT page lists the family from 25 to 630 mm², while individual models cover narrower bands such as 25–95, 35–150, 95–240, 120–300, 185–400, and 500–630 mm². The buyer must select the individual row that covers the actual conductor.
The listed range still needs confirmation for the conductor’s material and construction. Ask the supplier for the applicable selection table and installation instructions, rather than relying only on the marking shown in a product photograph.

CONWELL BLMT mechanical cable lug; the exact conductor range and palm-hole option are model-specific.
For low- and medium-voltage terminations, the shear-bolt mechanical lug option lists a high-strength aluminum-alloy body, aluminum-alloy bolts, tin-plated surface, and individual cross-section bands. CONWELL states that the family is intended for low- and medium-voltage cable terminations up to 35 kV. Project approval should still be based on the exact model documentation.
The palm is part of the electrical and mechanical interface. Obtain the switchgear, transformer, motor, or busbar drawing before releasing the purchase order.
Record the stud diameter and the required clearance-hole diameter. A model suffix such as 13 or 17 may indicate a nominal palm-hole dimension, not an M13 or M17 stud. Verify the manufacturer’s dimension drawing and the equipment fastener. An oversized hole reduces seating area; an undersized hole creates site rework.
Confirm whether the terminal pad requires one hole or two. For a two-hole interface, specify both hole diameter and center-to-center pitch. Also define the permitted orientation. Do not drill a second hole or enlarge a palm on site unless the equipment and lug manufacturers approve the change.
Check that the palm sits fully on the equipment pad without contacting barriers or adjacent hardware. Palm width, thickness, edge distance, flatness, and available washer area affect fit. The selected bolt length must accommodate the terminal pad, lug palm, washers, locking arrangement, and nut engagement.
Compare overall lug length, barrel diameter, palm offset, bolt-head access, and cable entry direction with the cubicle drawing. Maintain the equipment manufacturer’s phase-to-phase and phase-to-earth clearances. The cable should enter the barrel without forcing the termination or violating its minimum bend radius.
Prioritize palm fit, phase-barrier clearance, tightening access, and cable routing. A narrow cubicle can reject an electrically suitable lug because the body or bolt head cannot be reached after the cable is positioned.
Verify the terminal pad material, stud arrangement, allowable cable direction, and any vibration or thermal-cycling requirements. If several parallel cables share one phase, confirm the permitted lug stacking arrangement with the transformer manufacturer.
Check the terminal-box opening, palm width, creepage and clearance, cable gland position, and resistance to vibration. The installation should not transfer cable weight or bending force into the equipment terminal.
Where several cable constructions and field conditions must be covered, ask for a documented mechanical connection solution rather than selecting from photographs or a generic size chart.
The purchase specification should define the installation evidence needed at handover. For shear-head designs, use the bolt sequence, holding method, and any insert or centering component stated by the manufacturer. Do not add an unapproved torque value after the head has sheared.
| RFQ field | What to submit |
|---|---|
| Cable | Manufacturer, designation, voltage class, conductor metal, shape, construction, class, cross-section, diameter, and quantity |
| Equipment interface | Terminal drawing, pad material, stud size, hole count, hole pitch, available palm width, and installation orientation |
| Space | Maximum lug envelope, phase barriers, cable-entry direction, bend-radius constraint, and tool-access restriction |
| Electrical system | Rated voltage, expected current, fault-duty requirement, and termination or insulation system |
| Required evidence | Dimension drawing, conductor selection table, installation instruction, material statement, applicable test report, inspection plan, and traceability requirements |
No. Cross-section is only one field. The exact model must also cover the conductor material, shape, construction, and class, while its palm and overall envelope must fit the equipment.
Only when the supplier’s table approves that conductor type. A range for round stranded aluminum cannot automatically be applied to sector, solid, compacted, copper, or fine-stranded conductors.
Do not read the hole dimension as a stud designation. Compare the actual hole diameter with the equipment stud and its specified clearance, washer, and bearing requirements.
Approve the exact lug model against the cable data sheet and equipment drawing. For a new interface, a sample fit check is useful before production quantities are released. Confirm the required test evidence and installation records at the same time.
For a mechanical cable lug selection guide tied to your project, submit the cable data sheet, conductor construction, equipment terminal drawing, voltage and fault-duty requirements, quantity, required delivery date, and document list through CONWELL’s contact page. The supplier response should identify the exact model, approved conductor range, palm dimensions, installation method, and supporting documents so the lug can be checked before procurement and installation.
Written by the CONWELL international trade team, led by Matt, General Manager, who brings more than 20 years of international trade experience and deep expertise in the power fittings industry. He also leads CONWELL's CNAS laboratory, overseeing product testing, quality control, and technical compliance.
TEL: +86-158-5877-7327
No. 16, Waixi Road, Lingang Economic Development Zone, Yueqing Bay Port Area, Yueqing City, Wenzhou City, Zhejiang Province, China
COPYRIGHT © 2025 ZHEJIANG KEYI ELECTRIC GROUP CO., LTD. ALL RIGHTS RESERVED.
We value your privacy
We use cookies to enhance your browsing experience, serve personalised ads or content, and analyse our traffic. By clicking "Accept All", you consent to our use of cookies.
Customise Consent Preferences
We use cookies to help you navigate efficiently and perform certain functions. You will find detailed information about all cookies under each consent category below.
The cookies that are categorised as "Necessary" are stored on your browser as they are essential for enabling the basic functionalities of the site. Show more
Necessary cookies are required to enable the basic features of this site, such as providing secure log-in or adjusting your consent preferences. These cookies do not store any personally identifiable data.
Functional cookies help perform certain functionalities like sharing the content of the website on social media platforms, collecting feedback, and other third-party features.
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics such as the number of visitors, bounce rate, traffic source, etc.
Performance cookies are used to understand and analyse the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Advertisement cookies are used to provide visitors with customised advertisements based on the pages you visited previously and to analyse the effectiveness of the ad campaigns.