A hot line clamp must match two conductors, an approved operating method, and a defined service duty. Selecting only by a broad cable range can produce a clamp that fits the main conductor but not the tap, cannot be handled by the crew’s stick, or is unsuitable for the planned temporary bypass or permanent transformer lead.
Start the RFQ with the network and work procedure, then use the CONWELL hot line clamp range to identify candidate designs. Energized installation must be authorized by the utility and performed by qualified personnel using the required cover-up, tools, PPE, approach distances, and job controls.
| Gate | Information to submit | Evidence to obtain |
|---|---|---|
| Main conductor | Material, type, cross-section, diameter, stranding, surface and condition | Exact main-groove compatibility |
| Tap conductor | Material, type, cross-section, diameter, load current and termination | Exact tap-groove compatibility |
| Work method | Rubber-glove or stick method, work position, reach and installation sequence | Approved tool interface and instructions |
| Electrical duty | System voltage, normal current, fault level and clearing time | Manufacturer’s declared ratings and applicable reports |
| Service duty | Permanent tap, temporary bypass, maintenance jumper or emergency connection | Written suitability and inspection or removal plan |
Record the main and tap conductors separately. For each side, provide the cable or conductor manufacturer, reference, metal, construction, nominal cross-section, actual outside diameter at the contact area, strand condition, and surface coating. AAC, AAAC, ACSR, copper, covered conductor, and insulated cable cannot be treated as interchangeable labels.
The main and tap ranges must each contain the proposed conductor. Overlap on a catalogue table is only the first check. Ask the supplier to confirm that the groove geometry, contact area, and clamping travel suit the exact conductor type and diameter without strand damage or an unstable contact position.
If the work involves covered conductor, state whether the approved procedure requires insulation removal and how the exposed section will be sealed or covered afterward. Do not assume that a bare-conductor clamp can pierce insulation.

The AH clamp has distinct main and tap contact areas; each side needs its own conductor confirmation.
State the metal on both sides before choosing an aluminium, copper-alloy, bronze, or purpose-designed bimetal interface. A suitable material combination must provide the required conductivity and control galvanic interaction in the actual environment. Do not use plating, joint compound, or a washer as an improvised substitute for an approved dissimilar-metal design.
CONWELL publishes the AH hot line tap clamp as an aluminium design for aluminium and ACSR conductors. Its public page identifies an aluminium-alloy body, tin-plated bronze eyebolt, and stainless-steel eyestem. These facts do not establish suitability for a copper tap, coastal exposure, or a particular current duty; request model-specific confirmation.
For polluted, industrial, or coastal locations, add the environmental category, contamination, expected moisture, and corrosion-document requirements to the RFQ. Ask how contact surfaces are prepared and which compound, if any, is specified by the manufacturer.
The installation method determines whether the crew can control the clamp safely and reach the tightening mechanism. Provide the utility procedure reference, rubber-glove or insulating-stick method, work position, approach direction, operating distance, and whether the clamp is installed from an aerial device or another approved platform.
For stick operation, identify the existing stick or clamp-stick model, end fitting, jaw or hook interface, working length, allowable mechanical load, and inspection status. The clamp eye must accept the tool without uncontrolled rotation or release. Confirm the installation direction, sequence, tightening indicator or torque instruction, and whether a holding tool is required for the tap conductor.

The operating eye must be checked against the crew’s approved stick head and the planned approach angle.
A clamp that can physically be reached by a hot stick is not automatically approved for energized installation. The connector design, work method, voltage exposure, cover-up plan, network condition, crew qualification, and utility authorization must all permit the task.
Do not infer current capacity from conductor range. Give the expected continuous and emergency current, duty duration, connection temperature limits, ambient conditions, and available fault current with protection clearing time. Ask the supplier to state the rating basis and provide the reports required by the project.
System voltage also affects the procedure, approach distances, insulating tools, and cover-up, even when the clamp is a conductive component rather than the worker’s primary insulation. State nominal and maximum operating voltage, phase-to-phase and phase-to-ground exposure, grounding arrangement, and any automatic-reclosing controls required by the utility procedure.
Specify the applicable standard by title and edition instead of writing “IEC compliant” or “utility grade.” The evidence must cover the offered clamp model, material combination, conductor application, and claimed electrical and mechanical duties.
For a permanent transformer lead or distribution tap, request confirmation for long-term outdoor service, thermal cycling, conductor movement, corrosion, and the utility’s maintenance policy. Include the final insulating cover, cable support, and inspection access in the design.
For a temporary bypass, specify the complete circuit: source clamp, load clamp, bypass cable, terminations, supports, phase identification, cover-up, switching sequence, load-transfer limits, monitoring, maximum installation period, and removal plan. A clamp approved for a permanent tap is not automatically suitable for repeated temporary installation, and a temporary clamp should not be left in permanent service without written approval.
Use the live working tools application overview to identify related components, then require a line-by-line statement of what the supplier has verified as one compatible assembly.
Draw the energized work zone and identify every exposed conductor, connector, crossarm component, insulator, and grounded surface that may be approached by the worker, clamp, tap lead, or tool. Select appropriate line hoses and insulating covers for the actual voltage exposure and geometry. Cover-up dimensions, overlap, closure, and interfaces should follow the approved work procedure and product instructions.
Check clearance around the operating eye, moving jaw, tap outlet, and installation tool. Confirm that the tap lead can be routed and supported without pulling the clamp sideways or interfering with adjacent phases.

The side view helps define tool access, clamp orientation, and the space required around the operating mechanism.
| RFQ section | Required entry |
|---|---|
| Network | Voltage, grounding, normal current, fault level, clearing time and environmental conditions |
| Main conductor | Material, type, cross-section, diameter, stranding, coating and surface condition |
| Tap conductor | Material, type, cross-section, diameter, load, route and termination |
| Operation | Work method, procedure, stick and head model, working length, approach direction and tightening control |
| Service | Permanent or temporary, installation period, switching sequence, inspection, monitoring and removal conditions |
| Documents | Controlled drawing, data sheet, installation instructions, material record, ratings, applicable test reports and traceability |
How do I confirm the main and tap conductor ranges for a hot line clamp?
Check the main and tap sides separately against the manufacturer’s table, then confirm conductor material, type, construction, nominal cross-section, and actual contact diameter. Both conductors must sit within the declared range for the exact model; an overlap in square millimetres alone does not prove a correct fit.
Can an aluminium hot line clamp connect a copper tap conductor?
Only if the exact clamp is designed and documented for that aluminium-to-copper interface. Plating, joint compound, or field-added hardware does not turn a same-metal clamp into an approved bimetal connection. State both conductor metals and obtain written material compatibility before ordering.
Can the same clamp be used for a permanent tap and a temporary bypass?
Do not assume so. Permanent duty may require long-term thermal, corrosion, and mechanical performance, while temporary duty adds repeated installation, removal, monitoring, and a defined service period. Ask the manufacturer to declare the permitted duty for the offered model and include it in the acceptance documents.
Does an operating eye mean the clamp is compatible with any hot stick?
No. Confirm the eye dimensions, stick or clamp-stick model, end fitting, head geometry, approach angle, working length, mechanical load, and installation sequence. The utility’s approved procedure must also permit that tool and clamp combination at the stated system conditions.
Approve a hot line clamp only when the exact main and tap conductors, material pairing, operating tool, electrical duty, service duration, cover-up arrangement, and acceptance evidence are documented. A broad size range or product family name cannot replace that interface review.
For a model check and quotation, send CONWELL your tap-connection data, including conductor sheets, network conditions, work-method reference, tool interface, permanent or temporary duty, quantity, and document list. Ask the supplier to identify every confirmed parameter and every project item that remains outside its scope.
Written by the CONWELL international trade team, led by Matt, General Manager, who brings more than 20 years of international trade experience and deep expertise in the power fittings industry. He also leads CONWELL's CNAS laboratory, overseeing product testing, quality control, and technical compliance.
TEL: +86-158-5877-7327
No. 16, Waixi Road, Lingang Economic Development Zone, Yueqing Bay Port Area, Yueqing City, Wenzhou City, Zhejiang Province, China
COPYRIGHT © 2025 ZHEJIANG KEYI ELECTRIC GROUP CO., LTD. ALL RIGHTS RESERVED.
We value your privacy
We use cookies to enhance your browsing experience, serve personalised ads or content, and analyse our traffic. By clicking "Accept All", you consent to our use of cookies.
Customise Consent Preferences
We use cookies to help you navigate efficiently and perform certain functions. You will find detailed information about all cookies under each consent category below.
The cookies that are categorised as "Necessary" are stored on your browser as they are essential for enabling the basic functionalities of the site. Show more
Necessary cookies are required to enable the basic features of this site, such as providing secure log-in or adjusting your consent preferences. These cookies do not store any personally identifiable data.
Functional cookies help perform certain functionalities like sharing the content of the website on social media platforms, collecting feedback, and other third-party features.
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics such as the number of visitors, bounce rate, traffic source, etc.
Performance cookies are used to understand and analyse the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Advertisement cookies are used to provide visitors with customised advertisements based on the pages you visited previously and to analyse the effectiveness of the ad campaigns.