An insulation piercing connector can reach its designed clamping point and still be wrong for the job. The usual causes are not complicated: the main or tap conductor falls outside the marked range, copper and aluminum compatibility was assumed, the cable construction was not checked, or the installer treated shear-head separation as the only acceptance criterion.
For an LV-ABC service tap, street-lighting branch, or distribution-line retrofit, insulation piercing connector installation should begin with the cable schedule and the connector’s model-specific instructions. The sequence below is a control framework for trained personnel. It does not replace the manufacturer’s installation sheet, the project method statement, or local rules governing energized work.

De-energized installation should be the default unless the selected connector, approved work method, employer procedure, and local regulations all permit another condition. A statement that an IPC can be installed on an energized conductor is model- and procedure-specific; it is not permission to perform live work. Record the isolation or energized-work authorization before installation starts.
Also confirm the connector’s intended system. A connector made for LV aerial bundled cable should not be transferred to consumer wiring, underground cable, covered MV conductor, or another cable construction merely because the conductor fits inside the body. The application scope, voltage class, cable standard, insulation construction, and environmental rating all need documentary support.
| Check | What to verify | Why it matters |
|---|---|---|
| Main conductor | Material, cross-section, stranded construction, insulation type and outside condition | The main and tap sides often have different permitted ranges. |
| Tap conductor | Material, cross-section, insulation, cut length and required entry depth | An undersized or partially inserted tap can remain loose after the head separates. |
| Material pairing | Al-Al, Cu-Cu or Al-Cu as stated for the exact connector | Blade material and sealing design cannot be inferred from the body shape. |
| Connector identity | Manufacturer, model, conductor ranges, lot, voltage/application and required standard | A visually similar model may use another torque or cable range. |
| Physical condition | No cracks, damaged seals, missing end cap, corrosion, contamination or previous installation marks | A damaged or previously used connector should not enter the work package. |
| Tools and documents | Correct socket, holding tool if specified, installation sheet, drawing and inspection form | Tool access and installation evidence need to be planned before climbing or isolating the circuit. |
Use the complete cable marking or an approved cable data sheet. Do not rely on a rough diameter measurement to substitute for conductor cross-section. If the cable is oval, compacted, multi-layered, weathered, or unmarked, obtain written confirmation before proceeding.
For an IPC specifically designed to pierce the insulation on both the main and tap sides, the normal answer is no. The teeth must pass through the intact insulation while the connector seals around the cable. Stripping the insulation can change the fit and compromise the sealing arrangement.
There are exceptions. Some cable systems have an outer sheath over individually insulated cores, and some connector designs accept a bare conductor on one side or require a removable insert. Follow the exact model instruction. Never strip extra insulation simply to force an out-of-range conductor into the connector. Replace the connector with the correct size.
The connector instruction sheet takes precedence, but a controlled LV-ABC installation usually follows this order:
An open-ended wrench can load the shear head unevenly or slip in restricted access. Use the tool type and socket size named in the instruction sheet. Impact tools should not be used unless the connector manufacturer has approved them for that model.
The shear head is designed to separate after the fastener reaches the connector’s predetermined installation condition. It helps control contact pressure without asking the installer to read a torque wrench at the pole. It does not prove that the selected connector was correct, that both conductors were fully inserted, or that the cable insulation was undamaged before work began.
Torque values are model-specific. CONWELL’s current product listing, for example, records KWEP-CT for a 16–95 mm² main and 1.5–16 mm² tap at 10 Nm, while KW101 is listed for a 16–95 mm² main and 1.5–10 mm² tap at 10 Nm. These values apply only to those listed models. They must not be copied to another IPC based on appearance.

If the head separates before the housing closes as shown in the drawing, the conductor slips, the tap is not fully seated, or the connector becomes distorted, stop the job. Quarantine the connector, photograph the condition, and request an engineering disposition. Do not fit another nut or reuse the connector as an improvised repair.
A practical inspection record should allow a supervisor to reconstruct what was installed without reopening the connector. At minimum, record:
| Record field | Required entry |
|---|---|
| Location | Pole, feeder, phase, circuit and asset reference |
| Connector | Manufacturer, model, lot/batch and quantity |
| Main conductor | Material, cross-section, cable type and insulation condition |
| Tap conductor | Material, cross-section, destination and insertion confirmation |
| Installation control | Circuit state, work permit, tool/socket and instruction revision |
| Acceptance | Shear head separated, body aligned, cap seated, no visible damage and no exposed conductor |
| Evidence | Before/after photographs, installer, reviewer, date and exception number |
Project specifications may also require continuity, resistance, thermal imaging after load stabilization, or periodic inspection. Define those tests in the inspection and test plan rather than adding an unverified field procedure at site.
CONWELL lists IPC models with different main/tap ranges and installation torques within its broader aerial cable accessories portfolio. The company’s LV overhead-line solution also places IPCs alongside the supporting and anchoring hardware required for a complete line.
Use the existing explanation of how an IPC works for basic product orientation. For procurement, request the exact model data sheet, installation instruction, drawing, applicable test evidence, packaging identification and inspection requirements. Category-level statements are not a substitute for model-level documents.
Not when the selected model is designed to pierce intact insulation on that side. Check both channels because some products or cable constructions require different preparation.
It confirms that the designated head reached its separation condition. Acceptance also requires correct model selection, full conductor insertion, proper alignment, intact sealing parts and a satisfactory visual inspection.
Do not tighten it unless the model instruction expressly tells you to do so. Additional tightening can damage the housing, conductor or contact system.
Assume no unless the manufacturer provides explicit written instructions allowing reuse. Piercing teeth, seals and torque-control parts may already have completed their installation cycle.
State the application, system voltage, main and tap conductor materials and cross-sections, cable construction, required standard and edition, installation condition, environmental requirements, quantity, packaging, drawings, instructions and test documents.
Stop when the model cannot be verified, either conductor falls outside the marked range, insulation is damaged, sealing parts are missing, the connector was previously used, or the shear head separates before the assembly reaches the position shown in the instruction.
For an installation-ready recommendation, send CONWELL the main and tap conductor material, cross-section, cable type and insulation, system voltage, application, circuit state during installation, project standard and edition, quantity, destination, required delivery date, and document list. Add photographs or cable data sheets where the marking is unclear. Contact CONWELL with these details so the reply can identify a model and the evidence that must accompany it.
Written by the CONWELL international trade team, led by Matt, General Manager, who brings more than 20 years of international trade experience and deep expertise in the power fittings industry. He also leads CONWELL's CNAS laboratory, overseeing product testing, quality control, and technical compliance.
TEL: +86-158-5877-7327
No. 16, Waixi Road, Lingang Economic Development Zone, Yueqing Bay Port Area, Yueqing City, Wenzhou City, Zhejiang Province, China
COPYRIGHT © 2025 ZHEJIANG KEYI ELECTRIC GROUP CO., LTD. ALL RIGHTS RESERVED.
We value your privacy
We use cookies to enhance your browsing experience, serve personalised ads or content, and analyse our traffic. By clicking "Accept All", you consent to our use of cookies.
Customise Consent Preferences
We use cookies to help you navigate efficiently and perform certain functions. You will find detailed information about all cookies under each consent category below.
The cookies that are categorised as "Necessary" are stored on your browser as they are essential for enabling the basic functionalities of the site. Show more
Necessary cookies are required to enable the basic features of this site, such as providing secure log-in or adjusting your consent preferences. These cookies do not store any personally identifiable data.
Functional cookies help perform certain functionalities like sharing the content of the website on social media platforms, collecting feedback, and other third-party features.
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics such as the number of visitors, bounce rate, traffic source, etc.
Performance cookies are used to understand and analyse the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Advertisement cookies are used to provide visitors with customised advertisements based on the pages you visited previously and to analyse the effectiveness of the ad campaigns.