An ADSS dead end clamp should not be selected by fiber count, span length, or a model name alone. Within CONWELL’s optical-cable range, several diameter windows overlap, while other models cover a different cable size altogether. The useful first decision is which references remain candidates for the named cable—not which has the largest breaking-load number.
This article compares the published fields for PA500, PAL1500D, PA39, and PA05, and identifies the missing confirmation for PA08. It focuses on dead-end model fit, not intermediate-pole suspension design or a complete route-wide hardware kit.
The following information was checked against CONWELL’s optical tension-clamp pages on 20 October 2026. A published breaking load is not an allowable working tension or proof of compatibility with every ADSS jacket in the diameter window.
| Reference | Published cable diameter | Published breaking-load field | Model-fit boundary |
|---|---|---|---|
| PA500 | 4.5–9 mm | 2.5/4 kN | Confirm the exact version and meaning of the two load values before specifying capacity. |
| PAL1500D | 12–15 mm | 15 kN | A different diameter window, not an automatic higher-load replacement for a small-cable clamp. |
| PA39 | 3–9 mm | 4 kN | Diameter overlaps PA500; cable construction, jacket, and grip evidence still need review. |
| PA05 | 1.5–6 mm | 2 kN | Confirm the proposed cable family and round-jacket fit; the size field alone is not an ADSS approval. |
| PA08 | Not verified for this comparison | Not verified | Obtain a current CONWELL drawing and specification before including it in an approved shortlist. |
Start with the fiber optic tension clamp range, then retain the complete supplier reference in the BOM. Similar PA model names from different manufacturers do not establish identical ranges, loads, or gripping geometry.
A nominal 5 mm cable falls inside the published diameter fields of all three references. That creates a dimensional shortlist, not three interchangeable choices. Submit the cable tolerance, jacket material, strength-member construction, and required tension to distinguish the candidates.
For an 8 mm cable, PA39 and PA500 remain within their published windows, while PA05 is excluded. The small-diameter round-cable anchor specifications list PA500’s load as “2.5/4 kN.” Do not silently use 4 kN as the capacity of every delivered PA500; ask which exact configuration and test record the quotation covers.
PA39’s category listing displays “3*9 mm,” but its product detail explicitly states 3–9 mm. Use the detail-page value for this initial comparison and request the current controlled drawing for final approval.
A nominal 13 mm cable falls within PAL1500D’s published window but outside those of PA05, PA39, and PA500. Conversely, a 5 mm cable is not qualified for PAL1500D by its higher catalog breaking-load value.
The larger-diameter optical cable anchoring specifications refer to PAL1500D. Preserve the D suffix: do not substitute the PAL1500 reference used for an ABC insulated-neutral-messenger application.
A cable between the verified windows also needs another reviewed option. For example, 10 mm is outside the four verified diameter windows in this table. Do not stretch a 9 mm limit or assume a 12 mm minimum can grip a smaller cable.
Several product descriptions mention access-network spans up to 100 m. That statement does not provide a complete model-specific loading basis. Cable mass, sag, temperature, wind, ice where applicable, and route geometry can produce different tensions at the same span.
The cable manufacturer must identify the relevant limits, including maximum allowable tension (MAT), rated tensile strength (RTS), and installation pulling limits using its own definitions and conditions. These cable values are not synonymous with the clamp’s breaking load.
Prysmian’s ADSS installation guidance identifies cable diameter, span distance, maximum installation tension, and maximum rated cable load as hardware-selection inputs. Its product-specific instructions should not be transferred to another cable or clamp as universal installation rules.
Ask the supplier to confirm the proposed clamp-and-cable combination against the project’s working and exceptional load cases. Do not select from an arbitrary fraction of RTS, apply a universal safety multiplier, or infer a permitted span from PA500’s model number.
Two cables with the same diameter may have different sheath materials, wall thicknesses, and internal strength-member arrangements. A grip that holds one cable without excessive deformation may be unsuitable for the other.
Request evidence for the named cable or a justified equivalent: permitted jacket construction, grip arrangement, slip criteria, mechanical loading conditions, and any required optical-performance checks. Absence of visible slip alone does not establish that the optical cable remains undamaged.
Keep catalog fields separate from generic descriptive text. Some CONWELL optical-clamp pages also contain LV-ABC wording in their technical-feature sections. Obtain optical-cable-specific confirmation rather than treating that text as proof of ADSS compatibility.
Identify terminal, sectioning, and angle locations on the route drawing. Where the design requires anchoring in two directions, record the arrangement and loads on each attachment. Do not reuse an intermediate suspension detail merely because its cable diameter matches.

CONWELL application image illustrating pole interfaces. It does not identify or validate any model in the fit table.
The fiber optic accessories solution overview can help organize the proposal. Confirm the bail or eye, hook clearance, permitted articulation, bracket, fixing method, and supporting structure for the selected dead-end assembly.

CONWELL UPB bracket example. Confirm the selected clamp’s attachment geometry and the complete fixing’s load requirements.
Can PA39 replace PA500 wherever the cable OD overlaps?
Not automatically. Confirm the exact cable, jacket, working tension, installation requirements, and supporting evidence. Overlap establishes candidates, not equivalence.
Is PAL1500D a stronger replacement for every small-cable model?
No. Its published cable window is 12–15 mm. A higher breaking-load field does not remove the minimum diameter requirement.
Can PA08 be ordered using another manufacturer’s table?
Do not transfer those values. Obtain the exact CONWELL reference, current dimensions, cable application, and mechanical evidence before specifying it.
Does a stated 100 m span replace sag-tension review?
No. The named cable and actual route conditions determine the loads. Have the designer and cable/hardware suppliers confirm the candidate against those conditions.
For an ADSS dead end clamp RFQ, send the cable datasheet, OD and tolerance, jacket construction, span and sag-tension data, MAT/RTS definitions, installation limits, pole position, attachment drawing, and quantities.
Ask CONWELL to confirm the candidate model against your ADSS cable. Request the exact version, permitted diameter and jacket, working-load basis, grip evidence, and attachment requirements in the response. Keep unresolved references out of the approved BOM until those fields are confirmed.
Written by the CONWELL international trade team, led by Matt, General Manager, who brings more than 20 years of international trade experience and deep expertise in the power fittings industry. He also leads CONWELL's CNAS laboratory, overseeing product testing, quality control, and technical compliance.
TEL: +86-158-5877-7327
No. 16, Waixi Road, Lingang Economic Development Zone, Yueqing Bay Port Area, Yueqing City, Wenzhou City, Zhejiang Province, China
COPYRIGHT © 2025 ZHEJIANG KEYI ELECTRIC GROUP CO., LTD. ALL RIGHTS RESERVED.
We value your privacy
We use cookies to enhance your browsing experience, serve personalised ads or content, and analyse our traffic. By clicking "Accept All", you consent to our use of cookies.
Customise Consent Preferences
We use cookies to help you navigate efficiently and perform certain functions. You will find detailed information about all cookies under each consent category below.
The cookies that are categorised as "Necessary" are stored on your browser as they are essential for enabling the basic functionalities of the site. Show more
Necessary cookies are required to enable the basic features of this site, such as providing secure log-in or adjusting your consent preferences. These cookies do not store any personally identifiable data.
Functional cookies help perform certain functionalities like sharing the content of the website on social media platforms, collecting feedback, and other third-party features.
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics such as the number of visitors, bounce rate, traffic source, etc.
Performance cookies are used to understand and analyse the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Advertisement cookies are used to provide visitors with customised advertisements based on the pages you visited previously and to analyse the effectiveness of the ad campaigns.